How it works
Log mean temperature difference: ΔTlm = (Tflow - Treturn) / ln((Tflow - Troom) / (Treturn - Troom)). At the nominal 75/65/20 °C, ΔTlm is 49.8 °C.
Real output = nominal output x (ΔTlm actual / 49.8)^n, where n is the radiator exponent from EN 442, about 1.3 for panel radiators (1.2 to 1.4 in datasheets).
Example: a radiator rated 1,000 W at 75/65/20 gives only about 510 W at 55/45/20, roughly half. This is why radiators often need to be bigger when you switch to a heat pump with low flow temperatures.
The tool also shows the nominal size you need for a given real heat demand.
Results are estimates for planning. Check product data sheets, local building rules and an engineer's calculations where required.
Frequently asked questions
Why is my radiator weaker than the datasheet says?
The datasheet value is at 75 °C flow and 65 °C return. With 55/45 °C or lower, typical for heat pumps and modern boilers, the output drops to about half or less.
What is a good return temperature?
For condensing gas boilers and district heating, aim for a return below about 40 °C. Low return temperature means better efficiency and lower bills.
What exponent n should I use?
Use the value from the datasheet. Panel radiators are about 1.3, convectors up to 1.4, and underfloor heating close to 1.1.