How it works
Rain flow (l/s) = roof plan area (m²) x rainfall intensity (l/s per m²). Use the area seen from above, not the sloped area. The Danish design value is 140 l/s per hectare, which is 0.014 l/s per m².
Simplified capacity per downpipe with a level half-round gutter and the outlet at the end: 100 mm gutter with 75 mm downpipe about 1.1 l/s (about 80 m²), 125 mm with 90 mm about 1.7 l/s (about 120 m²), 150 mm with 110 mm about 2.8 l/s (about 200 m²) and 190 mm with 110 mm about 4.0 l/s.
We split the roof between the sides with gutters, pick the smallest gutter that one downpipe per side can handle, and add downpipes so no gutter run is longer than about 12 m from an outlet. Check the gutter maker's own table for the final choice.
Results are estimates for planning. Check product data sheets, local building rules and an engineer's calculations where required.
Frequently asked questions
What size gutter does a normal house need?
A typical gable-roof house of 100 to 150 m² uses 100 to 125 mm gutters with one or two downpipes per side.
Should I use the sloped roof area?
No. Rain falls vertically, so the plan area seen from above is what counts. A steep roof facing the wind can catch a bit more, which the safety in the table covers.
Where should the downpipe go?
An outlet in the middle of a gutter run roughly doubles the capacity compared with one at the end, because water flows from both sides.