Heat demand (W) = room volume (m³) x factor (W per m³ per °C) x temperature difference. The temperature difference is indoor temperature minus the design outdoor temperature, which is minus 12 °C in Denmark (20 - (-12) = 32 °C).
Factors used: old house with little insulation 1.4, average house from the 1960s to 1980s 1.0, newer house (1990s to 2010s) 0.6, low-energy house built to BR18 0.35 W/m³ °C. At 32 °C this is about 45, 32, 19 and 11 W per m³.
The radiator suggestion adds your safety margin (10 to 20 % is common) for heating up after night setback. Radiator outputs in datasheets are often at 75/65/20 °C; at lower flow temperatures, as with a heat pump, the real output is lower, so check with the radiator output calculator.
This is a rough estimate. Rooms with large windows, several outside walls or a cold floor lose more. A proper calculation follows DS 418.
Results are estimates for planning. Check product data sheets, local building rules and an engineer's calculations where required.
Frequently asked questions
How many watts per m² do I need?
As a rough guide, old houses need 80 to 120 W/m², average houses 60 to 80 W/m², new houses 30 to 50 W/m² and BR18 houses under 30 W/m² on the coldest day.
What design outdoor temperature should I use?
Denmark uses minus 12 °C. Other countries in Northern Europe use minus 10 to minus 20 °C depending on climate.
Is this enough to size a heat pump?
No. Use it for single rooms and radiators. For a heat pump, use the house's actual energy use or a full heat loss calculation by an installer.