How it works
Single-phase: ΔU = 2 x L x I x ρ / A. Three-phase: ΔU = √3 x L x I x ρ / A. L is the one-way length in metres, I the current, A the cross-section in mm² and ρ the resistivity: 0.0225 Ω·mm²/m for copper and 0.036 for aluminium at operating temperature (about 70 °C).
The percentage is ΔU divided by the supply voltage (230 V single-phase, 400 V three-phase). A common guideline is max 3 % for lighting and 5 % for other circuits, counted from the meter to the furthest point.
We assume a resistive load (cos phi 1) and ignore cable reactance, which is fine for cables up to about 95 mm². The tool also finds the smallest standard cross-section that keeps the drop under your limit.
Safety: voltage drop is only one check. The cable must also handle the current and the fuse. In Denmark fixed installations must be designed and made by an authorised electrician (autoriseret elinstallatør).
Results are estimates for planning. Check product data sheets, local building rules and an engineer's calculations where required.
Frequently asked questions
What is an acceptable voltage drop?
A widely used limit is 3 % for lighting and 5 % for other uses from the origin of the installation. Long runs to garages, sheds and EV chargers are where it usually becomes a problem.
Is the length one way or both ways?
Enter the one-way cable length. The formula already doubles it for single-phase because the current flows out and back.
Why does aluminium need a bigger cable?
Aluminium conducts about 60 % as well as copper, so you need roughly 1.6 times the cross-section for the same voltage drop.