How it works
Single-phase: I = P / (U x cos phi). Three-phase: I = P / (√3 x U x cos phi), where U is the line voltage (400 V in Europe). P is the real power in watts and cos phi is the power factor: 1 for heaters, about 0.8 to 0.9 for motors and heat pumps.
Example: 3 kW on 230 V with cos phi 1 gives 3000 / 230 = 13 A. The same 3 kW on three-phase 400 V is only about 4.3 A per phase.
The suggested fuse is the smallest standard size (10, 13, 16, 20, 25, 32, 35, 50 or 63 A) that is at least the load current. The cable must also be rated for that fuse, and motors may need a slower fuse type for the start current.
Safety: this is a guide. In Denmark new circuits and fixed connections must be installed by an authorised electrician (autoriseret elinstallatør).
Results are estimates for planning. Check product data sheets, local building rules and an engineer's calculations where required.
Frequently asked questions
How many amps is 3 kW?
About 13 A on single-phase 230 V and about 4.3 A per phase on three-phase 400 V, assuming a power factor of 1.
What fuse do I need for an 11 kW EV charger?
An 11 kW charger runs on three-phase 400 V at 16 A per phase, so it normally sits on a 16 A three-phase circuit with a type A or B RCD as the charger maker requires.
What is cos phi?
The power factor: the share of the current that does useful work. Heaters are close to 1, motors and old fluorescent fittings lower. A lower power factor means more current for the same kW.