How it works
The cable's current rating Iz depends on how well it can lose heat. A cable buried in thermal insulation gets hottest, one in conduit on a wall is in the middle, and one clipped direct or in free air is coolest. We use simplified values for PVC copper cable at 30 °C, based on the IEC 60364-5-52 methods A1, B1 and C.
The rule is I (load) ≤ In (fuse) ≤ Iz x correction factor. We add a 10 % margin on the fuse size, as needed for ordinary fuses (gG), so 1.5 mm² ends up on 10 to 13 A and 2.5 mm² on 16 A circuits. Use the correction factor for several cables bundled together or a warm room (for example 0.7 for four circuits bunched, 0.87 at 40 °C).
Example: 16 A single-phase in conduit needs at least 2.5 mm² copper (rated about 24 A in this method).
Guide only: the real choice also depends on voltage drop, short-circuit protection and the cable type. In Denmark fixed installations must be dimensioned by an authorised electrician (autoriseret elinstallatør).
Results are estimates for planning. Check product data sheets, local building rules and an engineer's calculations where required.
Frequently asked questions
What size cable for a 16 A circuit?
Normally 2.5 mm² copper, and 1.5 mm² only for 10 or 13 A circuits laid in good conditions. Long runs or bundled cables can push you to 4 mm².
What cable for an 11 kW EV charger?
16 A three-phase usually means 2.5 mm² for short runs and 4 to 6 mm² for longer ones because of voltage drop. Check with the voltage drop calculator.
Why is cable in insulation rated lower?
Thermal insulation traps the heat, so the copper reaches its 70 °C limit at a much lower current than in free air.